Hydraulic Components
SDC / DHC
232
EN2H-0221GE51 R0812
The input button can be used to modify the room temperature set
at the central device by +/-6 K referenced to the central position.
Turn clockwise: Temperature increase
Turn anti-clockwise: Temperature decrease
The indicator display is comprised of three LEDs. The possible
states are listed in the table below:
Control mode/Function Moon LED Clock LED Sun LED
Automatic
OFF
ON
OFF
Permanent heating
OFF
OFF
ON
Permanent reduction
ON
OFF
OFF
Start-up phase
BRIEF
FLASHING
BRIEF
FLASHING
BRIEF
FLASHING
Error at address setting
FLASHING ON
ON
Bus fault as well as
indication when
parameters are disabled
ON
FLASHING ON
Party (can be set via
central device)
OFF
OFF
FLASHING
Absent (can be set via
central device)
FLASHING OFF
OFF
Holiday (can be set via
central device)
OFF
Flash
OFF
Definition:
Flashing:
0.8 sec. on and 0.8 sec. off
Brief
flashing:
0.08 sec. on and 0.7 sec. off
Flash:
0.08 sec. on and 1.4 sec. off
The operation indication is updated immediately after adjustment
when adjusted at the SDC 10 and at the latest after about 20 sec.
after adjustment when adjusted at the central device.
In all other control modes not defined in the table above, all three
LEDs are activated.
Room setpoint
correction
Display
NOTE
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......