Operation
SDC / DHC
100
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
06
Sensor operating
mode
1
Burner switch-off in case
of defect
1
2
External burner switch-
off
3
Burner enable in case of
defect
07
Minimum burner
runtime
0 ... 20 min
2
08
Burner switching
differential I
One stage: 2 ... 30 K
6
Two stages: 2 ... (setting value of
parameter 09 – 0.5 K)
09
Burner switching
differential II (not if
parameter
01 = 2)
(setting value of parameter 08 +
0.5) to 30 K
8
10
Connection delay
stage II
0 ... 60 min (0 = 10 s)
0
11
Boiler start-up
relief stage II
1
Unlimited enable during
start-up relief
2
2
Time-out during start-up
relief