SDC / DHC
Operation
EN2H-0221GE51 R0812
97
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
11
Constant tem-
perature setpoint
(only if output was
set to constant
regulator)
10 ... 95°C
20
12
Minimum
temperature limit
10°C to setting value of
parameter 13
20
13
Maximum
temperature limit
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
75
14
Temperature
increase of heating
circuit
–5 ... 20 K
Mixed
heating
circuit = 4
15
Follow-up time of
pump
0 ... 60 min
5
16
Screed function
OFF
OFF
1
Functional heating
2
Screed-drying heating
17
Return maximum
temperature limit
10 ... 90
°
C
90
18
P part X
P
1 ... 50 %/K
2
19*
Sampling time T
s
1 ... 600 s
20
20
I part T
n
1 ... 600 s
270
21
Actuator runtime
10 ... 600 s
120
22*
Actuator end
position function
1
Continuous control
signal in end position
1
2
Control signal
suppressed at end
position (actuator de-
energised)
23
Room control C-
factor (SDW 30
only)
1 ... 100
8
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......