SDC / DHC
Operation
EN2H-0221GE51 R0812
105
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
11
Return limit of
district heating
valve
0
Temperature
(parameters 12 through
15 are not displayed)
0
1
Volume flow and
temperature (parameters
12 through 14 are not
displayed)
2
Heat output and
temperature (parameters
13 through 15 are not
displayed)
12*
Calibration of heat
output
1 ... 9999
1
13*
Calibration of
volume flow
1 ... 9999
1
14*
Maximum heat
output
1 ... 9999 kW
9999
15*
Maximum volume
flow
0,01 ... 99.99 m
3
/h
99.99
* OEM
5.4.8 "Return increase" menu (RETURN CONTR)
The parameters in this menu refer to special settings with regard
to the increase in return temperature with heat generators.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Return temperature
setpoint
10 ... 95°C
20
02
Switch-off
differential
1 ... 20 K
2
03
Follow-up time of
pump
0 ... 60 min
1
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......