SDC / DHC
Hydraulic Components
EN2H-0221GE51 R0812
179
of room setpoint, thermostat function, room controller setpoint
etc.).
Switch-over from heating mode to cooling mode:
If the outside temperature is greater than summer switch-off (see
"System Parameters", summer parameter) and the switch-on
temperature for cooling, the cooling function is active.
If the outside temperature is lower than the summer switch-off and
the cooling switch-on temperature of cooling –1 K, the cooling
function is not active. A switching differential is required.
With the cooling function active, the "cooling switch-over" output
in the "Hydraulics" menu, parameter 06/07, setting 25 = ON. This
is switched on inversely via an input on the heat pump. If cooling
mode is interrupted due to the switching conditions of the timer
(ECO lowering phase), the output switches OFF, even if the
switching conditions are present otherwise.
Heating circuit correction:
For cooling operation, the mixed heating circuit corrects to the
setpoint temperature at the flow sensor (see the "Heating Circuit"
menu, heating circuit cooling setpoint temperature parameter) and
functions as a heating controller.
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......