SDC / DHC
Operation
EN2H-0221GE51 R0812
107
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
12
Density of medium 0.8 ... 1.2 kg/L
1.05
13
Heat capacity of
medium
2 ... 5 KJ/kgK
3.6
15
Test cycle of solar
charging
switchover
1 ... 60 min
10
16
Switchover tem-
perature
20 ... 110 °C
75
5.4.10 "Solid" menu (SOLID FUEL)
The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Minimum
temperature
20 ... 80 °C
60
02
Maximum
temperature
30 ... 100 °C
90
03
Switch-on
differential
(Setting value of parameter
04 + 3 K) to 20 K
10
04
Switch-off
differential
2 K to (setting value of parameter
03 – 3 K)
5
05
Heat generator
cycle inhibitor
OFF, 2 to 180 min
OFF
5.4.11 "Buffer" menu (BUFFER)
The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......