SDC / DHC
Operation
EN2H-0221GE51 R0812
101
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
13
Lead time of boiler
circuit pump or
parallel heat
generator enable
(only with
appropriate
configuration in the
"Hydraulics"
menu)
0 ... 10 min
0
14
Follow-up time of
boiler circuit pump
(only with
appropriate
configuration in the
"Hydraulics"
menu)
0 ... 60 min
2
15
Follow-up time of
feeder pump (only
with appropriate
configuration in the
"Hydraulics"
menu)
0 ... 60 min
2
16
Exhaust gas
temperature
monitoring (only
with appropriate
configuration in the
"Hydraulics"
menu)
OFF
Display of exhaust gas
temperature only
OFF
0 ... 60
min
Heat generator lock if
limit value is exceeded
for set time
SLT
Heat generator lock if
limit value is exceeded
17
Exhaust gas limit
value (only with
appropriate
configuration in the
"Hydraulics"
menu)
50 ... 500°C
200