Operation
SDC / DHC
106
EN2H-0221GE51 R0812
5.4.9 "Solar" menu (SOLAR)
The parameters in this menu refer to special settings with regard
to the solar applications.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Switch-on
differential
(Setting value of parameter
02 + 3 K) to 30 K
10
02
Switch-off
differential
2 K to (setting value of parameter
01 – 3 K)
5
03
Minimum runtime
of solar charging
pump
0 ... 60 min
3
05
Buffer maximum
temperature limit
20 ... 110°C
75
06
Operating mode
1
Priority operation
2
2
Parallel operation
3
Priority operation of hot-
water circuit
4
Priority operation of
buffer
07
Heat generator
cycle inhibitor
(only if parameter
06 = 1)
OFF, 0.5 to 24 h
OFF
08
Solar priority
parallel switchover
OFF, 1 to 30 K
OFF
09
Heat balance
OFF
No heat balancing
OFF
1
Heat balancing via flow-
through calculation
2
Heat balancing via pulse
input
10
Reset heat
balance
SET by pressing the input button
–
11
Volume flow
0 ... 30 L/min or L/pulse
0
Содержание DHC
Страница 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Страница 2: ...EN2H 0221GE51 R0812 ...
Страница 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Страница 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Страница 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Страница 160: ...Hydraulic Components SDC DHC 160 EN2H 0221GE51 R0812 5 4 8 Return increase menu RETURN CONTR Pg 105 See also ...
Страница 261: ......