47
Modules Types
Currently, only the ControlEdge 900 UIOM is supported. Refer to the
I/O module type section.
Device Replacement
CAUTION: Explosion hazard. Removal and Insertion Under Power
is not supported in Division 2/ Zone 2. CPM and/or EPM removal
under power is not supported. The up/down rocking motion
required to remove the module causes intermittent
communications to other modules resident in the same rack. It is
recommended that before removing an active CPM or EPM, the
user first disconnects the power supply in the rack (associated
with the CPM or EPM to be removed) from the source main
power.
Replacing a non-redundant or unsynchronized
primary UOC-CPM
ATTENTION: This procedure can only be performed while off-
process.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require downloading
appropriate configuration data to the replaced component
through Control Builder.
Wear an ESD wrist strap and observe static precautions.
Before replacing a non-redundant or unsynchronized primary UOC-
CPM:
n
Make sure all UOC configuration data and operator commands
are up to date within saved checkpoints or uploaded Control
Builder data. If not, save checkpoint, upload to Control Builder or
both.
n
It is recommended to bring the process to a safe and orderly
shutdown.
You will need a #2 Phillips screwdriver.
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...