8. Set the new CPM’s mode switch position to STOP (to enable
firmware update).
9. Using an external (user-supplied) switch, re-connect the power
supply in the rack (associated with the new CPM) to the source
main power.
10. Optional-for IPsec enable system, setup certificates and IPsec
policy in the CPM. See "Setup certificates and IPsec policy in
PLC/RTU" in
ControlEdge PLC and ControlEdge RTU Network and
Security Guide
for more information.
11. Use the ControlEdge Builder to load firmware to the new CPM to
match the version that is running in the primary redundant
partner CPM.
12. Check the redundancy synchronization state by monitoring the
role LED of the primary or secondary CPM.
13. Switch the new secondary CPM’s mode switch position to match
the primary redundant partner CPM.
Replacing a primary PLC-CPM
ATTENTION: Replacing a synchronized primary CPM can be
performed while on-process or off-process.
Replacing an unsynchronized primary CPM can only be
performed off-process.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require firmware update
and/or downloading appropriate configuration data to the
replaced component through ControlEdge Builder.
Wear an ESD wrist strap and observe static precautions.
You will need a #2 Phillips screwdriver.
Replacing an unsynchronized primary PLC-CPM
n
It is recommended to first establish redundancy synchronization
between the redundant controllers (when possible) and follow the
procedure to replace a synchronized primary PLC-CPM below.
n
When primary CPM on-process replacement is either not required
or not possible due to inability to synchronize the redundant
controllers, follow the off-process procedures in
section.
30
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...