A 15K shunt resistor and a 7.5K series resistor are required closed to
the contact in field side. Refer to the following block diagram of this
channel configuration, and a field wiring example.
ATTENTION:
For Channels that are configured with a debounce, the UIO will
declare that the channel has changed state if all the
consecutive samples are in the new state for the configured
debounce time period.
Field wiring for Digital Output
When UIO is configured as a Digital Output, the channel can supply
up to 0.5A to the field. See the following table for the specification of
DO.
Table 5-18: UIO Specification for DO
Item
Description
Open wire detection
Configurable
Short circuit detection
Enabled by default and un-configurable
Maximum (resistive Load)
500mA
Minimum Load
20mA with OWD and 0mA without OWD
Maximum load capacitance
1 uF
Voltage Drop
< 1 V (at 500mA)
Off Current
< 0.1mA
Lead breakage test current
Approx. 10 mA
Output Current
0 - 23 mA
TIP:
If a Universal I/O Channel configured as Digital Output reports
an “OP Fail in circuit/field wire” alarm, the most likely cause of
the alarm is a broken wire. The user should check the continuity
of field wiring. It is suggested to enable Line Monitoring for
DOs so that the Event Log can clearly identify the problem as a
possible wire break.
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...