n
Cable lengths specified in this guide are absolute. When planning
for routing of cables and wires, be certain to include vertical and
horizontal routing within cabinets, raceways, and conduits.
n
Minimize the length of I/O wiring. Racks and wiring should also be
located away from adverse environmental conditions such as
sources of RFI, EMI, and away from areas with high levels of
moisture, dust, and corrosive materials.
n
For a Star network topology, a switch is required between the CPM
and multiple I/O rack.
n
One fiber optical converter can be added to connect the switch
and a remote rack.
n
For a Star network topology, a redundant switch is optional. The
I/O network is a private network and other devices including
health monitor application, must not connect to it, or it may result
in critical performance and security issues.
Fiber Optics Recommendations
Honeywell recommends to use the fiber optic cable for distances
longer than 100m. Equipment tested with the fiber optic cable is
listed in the following table:
Table 6-3: Fiber optics equipment recommendations
Items
Description
Ethernet
Switch
MOXA Unmanaged Ethernet Switch EDS-308-MM-SC with (6) 10/100
Ethernet ports, (2) multi-mode fiber ports with SC Connectors (require
24VDC power)
Fiber
optic
converter
MOXA Media Converter model IMC-101-M-SC with (1) 10/100BaseT (X)
to 100BaseFX multi-mode fiber port with SC connectors (require 24
VDC power)
Fiber
Cable
Multi-mode, Duplex, 62.5/125 with SC connectors on both ends
Copper
Ethernet
Cable
Shielded CAT5 Ethernet
FO
Connector
SC Type
154
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...