but if operating circumstances permit, disconnecting power from
the rack is the preferred option. Plan and develop an action
sequence before beginning the replacement procedure. Primary
considerations include:
When replacing I/O module, the voltages to the modules must be
disconnected at the field device before removing the terminal
block from the module.
Loss of control/monitoring in a running process - Each signal at
each of the terminals for an I/O module has a specific function.
Any or all of the signals may be vital for safely controlling a
process. Determine the functions of all signals to the modules
and know the potential consequences of losing each. If possible,
transfer control to alternate mechanisms; otherwise, bring the
process to a safe and controlled shutdown.
You will need a #2 Philips screwdriver.
To replace an I/O module:
CAUTION: Explosion hazard. Removal and Insertion Under Power
is not supported in Division 2/ Zone 2.
1. Disconnect all signals from power sources. Use a meter to ensure
that all voltages are disconnected.
2. If a power-down replacement procedure is opted, also disconnect
power from the rack, using the (user-supplied) switch in the
source main power.
3. Loosen the captive screws at top and bottom of the module;
loosening the screws will cause the terminal block to be partly
extracted from the module connector. Remove the terminal block
from the module.
CAUTION: The UIO module will continue to drive the
configured failsafe output if the UIO module is removed
along with the terminal block with the field power not de-
energized. So it is recommended to de-energize field power
before UIO module removal.
4. Using the extractor loop on the cover of the module, pull the
module from the slot with a long flat-tip screwdriver an extraction
lever. as shown in the following illustration.
162
Содержание ControlEdge 900 platform
Страница 6: ...6 Contents ...
Страница 12: ...12 Chapter 1 About this guide ...
Страница 52: ...52 ...
Страница 57: ...57 One Slot Rack 1 CPM 1 EPM 1 P S 1 RM ...
Страница 59: ...59 One Slot Rack ...
Страница 62: ...Figure 5 7 Rack dimensions with redundant power supply 62 ...
Страница 75: ...75 c Insert the Ethernet cables and mount the security cover for the EMP ...
Страница 76: ...d Optional mount a wire security seal The user should get a wire security seal themselves 76 ...
Страница 124: ...Figure 5 31 Universal Analog Input Wiring Figure 5 32 Examples of RTD Input Wiring 124 ...
Страница 125: ...125 Figure 5 33 Analog Input Wiring Eight TCs Figure 5 34 Analog Input Wiring Eight Resistance Inputs ...
Страница 136: ...Settings using input 1 as example Single ended factory setting Differential Figure 5 46 Pulse Counting Wiring 136 ...
Страница 137: ...137 Figure 5 47 Pulse Outing Wiring Figure 5 48 Frequency Wiring ...
Страница 138: ...Figure 5 49 Quadrature Differential External Power Wiring Figure 5 50 Quadrature Single Ended External Power Wiring 138 ...
Страница 144: ...Figure 5 57 16 point High Level Analog Input Wiring 144 ...
Страница 147: ...147 Figure 5 60 AC DC Isolated Input Module Wiring ...
Страница 148: ...148 ...
Страница 168: ...168 ...
Страница 178: ...178 Chapter 8 Diagnostics and Troubleshooting ...
Страница 221: ...Appendix A Installing RTP RTP Internal schematic Applies to UAI Figure A 13 Analog Input RTP Internal schematic 221 ...
Страница 222: ...Appendix A Installing RTP 222 ...
Страница 227: ...Appendix A Installing RTP Relay Output RTP Internal schematic 227 ...