Section 5: Diagnostic Commands
5-3
V
= Power line voltage bad, not reported
(reporting window not expired)
^
= Power voltage restored, not yet reported
B
– Represents battery condition as follows:
+
= Battery voltage acceptable
–
= Battery voltage below 5.7V ±5%
Flt
– Represents radio faults:
OK
= Normal ; No fault
I
= No network connectivity over IP and fault
time has expired
i
= No network connectivity over IP and fault
time has NOT yet expired.
G
= No network connectivity over GSM and
fault time has expired.
g
= No network connectivity over GSM and
fault time has NOT yet expired.
NOTE:
The 7720P will not operate if the power line
voltage is removed.
Bat NLd: x.xxV
Bat Ld: x.xxV
Battery Voltage Display
The voltage levels of the module's battery can be viewed
on the 7720P. The first line of the display shows the
voltage level of the battery with no load. The second
line of the display shows loaded battery voltage. An
asterisk (*) next to the voltage indicates that this is
below the accepted level.
Press the [Space] key to go to the next field.
Battery Charger
OK
Battery Charger Status Display
The status of the battery charger circuit can be viewed
on the 7720P. The status is either OK or NOT OK.
Press the [Space] key to go to the next field.
Line Voltage
xx.xxV
Line Voltage Display
The line voltage can be viewed on the 7720P. An
asterisk (*) next to the voltage indicates that this is
below the accepted level.
Press the [Space] key to go back to the System Status
Display.
[T]
Test Msg Sent
Test Alarm
Sends a Test alarm to AlarmNet. Functional for a
registered
module only. If the device is not registered, a
message is displayed indicating that the command
cannot be executed.
[X]
Reset CPU Y/N
Reset the module.
Pressing [N] returns to diagnostic mode (blank screen =
enter next command or escape).
Pressing [Y] resets the module (blank screen = reset
complete).
[
↑
]
(UP arrow)
Registering …
Registration
Registers a programmed module with AlarmNet
.
[
↓
]
(DN arrow)
Enter PIN#
Registration with PIN for Replacement Module
Registers a replacement module with AlarmNet, once
programmed, using the existing PIN #.
Содержание AlarmNet GSMBR
Страница 2: ......
Страница 38: ...GSMBR iGSMBR Installation and Setup Guide 3 22 ...
Страница 50: ...GSMBR iGSMBR Installation and Setup Guide A 2 ...
Страница 54: ...GSMBR iGSMBR Installation and Setup Guide C 2 ...
Страница 57: ...NOTES ...
Страница 58: ...NOTES ...
Страница 59: ...NOTES ...
Страница 60: ...NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...