Section 3: Programming
3-15
Programming for Zone Trigger, 4204 and Two-4204 Modes
PROMPTS
ZONE
TRIG.
4204/
2-4204 ENTRY
OPTIONS
DESCRIPTION
Prompt 22 appears for the iGSMBR only.
22
IP Flt Time
(00 mins)_
[00-99]
In the event there is a loss of contact with the
network over the Ethernet connection, enter the
time delay (in minutes) before the
communica-
tions module
notifies the central station. IP
failure will always be sent to the central station
as Primary Communication Path Failure.
23
GSM Flt Time
(00 mins)_
[00-99]
In the event the module detects a communication
path failure, enter the time delay (in minutes)
before the
communications module
notifies the
central station. For an iGSMBR, a GSM failure
will always be sent to the central station as
Secondary Communication Path Failure. For a
GSMBR, a GSM failure will be sent to the
central station as a Primary Communication
Path Failure.
Prompt 24 appears for the iGSMBR only.
24
Notify Panel Of_
(Neither Fault)_
[Neither
fault]
[Both IP
and GSM
Faults]
If "Both IP and GSM Fault" is selected, the
device will only notify the control panel if both
communication paths fail, but will always send
notification of either failure to the central
station.
NOTE:
The fault relay output (if programmed)
will be triggered only if "Both IP and GSM
Faults" is selected.
Press the [Space] key to scroll through choices.
25
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault. For
conditions that trip the fault relay refer to
Module Supervision Features
in Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
26
Pwr Loss Rpt Y/N
(Y)_
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after
power is restored.
Suggested Setting:
When using a transformer
and battery, set to "Y".
When using a LYNXR-I series control set to "N".
27
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low battery report when a low battery
condition exists. A low battery restore is sent
when the condition clears.
Suggested Setting:
When using a transformer
and battery, set to "Y".
When using a LYNXR-I series control set to "N".
28
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the module detects
a tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
Содержание AlarmNet GSMBR
Страница 2: ......
Страница 38: ...GSMBR iGSMBR Installation and Setup Guide 3 22 ...
Страница 50: ...GSMBR iGSMBR Installation and Setup Guide A 2 ...
Страница 54: ...GSMBR iGSMBR Installation and Setup Guide C 2 ...
Страница 57: ...NOTES ...
Страница 58: ...NOTES ...
Страница 59: ...NOTES ...
Страница 60: ...NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...