Section 3: Programming
3-17
Programming for Zone Trigger, 4204 and Two-4204 Modes
PROMPTS
ZONE
TRIG.
4204/
2-4204 ENTRY
OPTIONS
DESCRIPTION
31
Telco Zone
(0)_
Zone Trig: [3-
7]
4204: [1-4]
2-4204: [1-8]
[0] = not
used
See Important Information Regarding Zone
Input Options on previous page.
Enter the zone number to be used for telco line
fault reports. This zone assignment must be
unique from the open/close zone selected in
Prompt 32.
Zone Trigger Mode:
If any zone is programmed
for "report only if armed," zone 7 cannot be used.
If LYNX Panic is enabled, zone 3 cannot be used.
4204 Mode:
If any zone is programmed for
"report only if armed," zone 4 cannot be used.
2-4204 Mode:
If any zone is programmed for
"report only if armed," or if tamper is enabled,
zone 8 cannot be used.
NOTE:
Connect the Telco line fault output (or
relay output programmed for "Telco line fault")
to the Telco zone.
32
Open/Close Zone
(0)_
Zone Trig: [3-
7]
4204: [1-4]
2-4204: [1-8]
[0] = not
used
Enter the zone number to be used for open/close
(arm/disarm) reports.
This zone assignment must be unique from the
Telco zone selected in Prompt 31.
Zone Trigger Mode:
If any zone is programmed
for "report only if armed," zone 7 cannot be used
as an open/close zone. If LYNX Panic is enabled,
zone 3 cannot be used.
4204 Mode:
If any zone is programmed for
"report only if armed," zone 4 cannot be used as
an open/close zone.
2-4204 Mode:
If any zone is programmed for
"report only if armed," or if tamper is enabled,
zone 8 cannot be used as an open/close zone.
NOTE:
Connect an open/close (arm/disarm)
trigger (or relay output) from the control panel to
the open/close zone.
33
Zn1 Trigger Type
(V+)_
•
(EOLR)
•
(V+)
•
(V–)
Selects the triggering method for this zone input.
Press the [Space] key to scroll through choices.
34
Restore Zn1 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 1.
35
Delay Zn1 (secs)
(00)_
[01-15]
[00] = no
delay
Defines the reporting delay in seconds for zone 1.
36
Rpt Zn1 ONLY if
Armed (N)_
[Y], [N]
Report alarms on zone 1 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; or zone 8 in 2-4204 mode) is triggered
(armed).
If [N], always reports alarms on zone 1.
37
Invert Zn2 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone
2 trigger; otherwise uses normal input signal.
38
Restore Zn2 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 2.
Содержание AlarmNet GSMBR
Страница 2: ......
Страница 38: ...GSMBR iGSMBR Installation and Setup Guide 3 22 ...