Section 3: Programming
3-7
Programming for ECP Mode
PROMPTS
ENTRY
OPTIONS
DESCRIPTION
Prompt 27 appears for the iGSMBR only.
27
IP Flt Time
(00 mins)_
[00-99]
In the event there is a loss of contact with the network
over the Ethernet connection, enter the time delay (in
minutes) before the communications module notifies
the central station. IP failure will always be sent to the
central station as Primary Communication Path
Failure.
28
GSM Flt Time
(00 mins)_
[00-99]
In the event the module detects a communication path
failure, enter the time delay (in minutes) before the
communications module notifies the central station.
For an iGSMBR, a GSM failure will always be sent to
the central station as Secondary Communication Path
Failure. For a GSMBR, a GSM failure will be sent to
the central station as a Primary Communication Path
Failure.
Prompt 29 appears for the iGSMBR only.
29
Notify Panel Of_
(Neither Fault)
[Neither
fault]
[Both IP and
GSM Faults]
If "Both IP and GSM Fault" is selected, the device will
only notify the control panel if both communication
paths fail, but will always send notification of either
failure to the central station.
NOTE:
The fault relay output (if programmed) will be
triggered only if "Both IP and GSM Faults" is selected.
Press the [Space] key to scroll through choices.
30
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault. For conditions that trip the
fault relay refer to
Module Supervision Features
in
Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
31
Pwr Loss Rpt Y/N
(Y)_
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
Suggested Setting:
When using a transformer and
battery, set to "Y".
When using a LYNXR-I series control set to "N".
32
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low battery report when a low battery
condition exists. A low battery restore is sent when the
condition clears.
Suggested Setting:
When using a transformer and
battery, set to "Y".
When using a LYNXR-I series control set to "N".
33
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.
Содержание AlarmNet GSMBR
Страница 2: ......
Страница 38: ...GSMBR iGSMBR Installation and Setup Guide 3 22 ...
Страница 50: ...GSMBR iGSMBR Installation and Setup Guide A 2 ...
Страница 54: ...GSMBR iGSMBR Installation and Setup Guide C 2 ...
Страница 57: ...NOTES ...
Страница 58: ...NOTES ...
Страница 59: ...NOTES ...
Страница 60: ...NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...