Installation and Setup Guide
4-10
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*85
Linked Zone Verification Timer
\Up and About
Linked Zone Timer Entry:
0 = 15 secs
6 = 2-1/2 min #+12 = 8 min
1 = 30 secs
7 = 3 min
#+13 = 10 min
2 = 45 secs
8 = 4 min
#+14 = 12 min
3 = 60 secs
9 = 5 min
#+15 = 15 min
4 = 90 secs
#+10 = 6 min
5 = 2 min
#+11 = 7 min
Up and About Timer Entry:
1 through 15 for number of hours
Linked Zone Timer:
Sets the maximum amount of
time in which two linked zones must be tripped in an
armed system to send an alarm message to the Central
Station. If only one linked zone is tripped during this
time, a trouble message (CID code 380) for that zone is
sent to the Central Station.
Assign linked zone pairs in zone list 4.
Up and About Timer:
1-15 hours. This option is part
of an Up and About schedule (event 12) that must be
programmed. The value in this field is the time within
which activity must occur within the overall scheduled
up and about time window. If no zones are faulted or
no key is pressed within the selected time period
during the scheduled Up and About time window, a
report is sent to the central station. This can serve as a
safety feature for elderly, infirm, or disabled persons.
See
Programming Installer and User Schedules
section for programming schedules.
*86
Cancel Verify Keypad Display /
AC Fail Dial Delay
Cancel Verify:
0 = no; 1 = yes
AC Fail Dial Delay
0 = random report time between 30 and 60
minutes after fail
1-6 = 10 to 60 minutes in 10-minute
increments (1 = 10 min, 2 = 20 min,
3 = 30 min, 4 = 40 min, 5 = 50 min,
6 = 60 min)
Cancel Verify Display
When enabled (1 = yes), this feature causes a
“
CANCELED ALARM”
display on the LCD keypad
under the following conditions:
•
After the kissoff of the cancel message to the Central
Station, indicating a successful transmission.
•
When an alarm is successfully canceled before the
Central Station received the Alarm message. E.g., if
an alarm is falsely triggered and the user presses
code + OFF before the dial delay time has expired,
the message will never go out to the CS.
•
When the Cancel report is not enabled and the
system is disarmed:
a.
before
dialer delay expires (alarm report not
sent) message “Canceled Alarm” is displayed.
b.
after
dialer delay expires message “Canceled
Alarm” not displayed.
AC Fail Dial Delay:
Select the desired report time for
AC fail reports
*87
Misc. Fault Delay Time
0 = 15 secs
6 = 2-1/2 min #+12 = 8 min
1 = 30 secs
7 = 3 min
#+13 = 10 min
2 = 45 secs
8 = 4 min
#+14 = 12 min
3 = 60 secs
9 = 5 min
#+15 = 15 min
4 = 90 secs
#+10 = 6 min
5 = 2 min
#+11 = 7 min
Used with zones assigned to a configurable zone type
with fault delay on (selected in alarm/trouble
processing prompt), and sets a zone response time of 15
seconds to 15 min. It can be assigned to zones with
sensors that provide a trouble indication when an oil or
gas tank is low, or similar applications for critical
condition monitoring where a non-alarm response is
desired and where the zone response time should be
very long to avoid reacting to normal transient faults.