Menu Mode Programming
5-7
Completing Zone Programming
When you have finished programming all zones, test each zone using the system’s TEST
mode.
Do not use the Sensor Sniffer Mode for checking wireless transmitting
devices
, as it will only check for transmission of one zone on a particular transmitter, NOT
the zones assigned to each additional loop.
NOTE:
Following the successful enrollment of each wireless device, note the device serial
number in the appropriate column on the ENROLLED TRANSMITTERS worksheet in the
Programming Form; then enter the other information (zone number, zone type, loop number,
etc.) relevant to that device.
∗∗∗∗
58 Expert Programming Mode Procedures
This method is designed for use by installers with previous experience in programming
ADEMCO control panels. This mode is also used to program wireless keys using pre-defined
templates.
Start Expert Programming mode by pressing
∗
58 while in Data Programming mode. The
following prompts are displayed:
PROMPT
VALID ENTRIES
EXPLANATION
SET TO CONFIRM?
0 = NO 1 = YES 0
Confirm?
0 = no
1 = yes
[
∗
] to continue
If 1 (Yes) is entered, the
XMIT TO CONFIRM
prompt appears later in
this procedure after
entering RF transmitter
serial and loop numbers,
and lets you confirm the
programming of each RF
transmitter.
We
recommend that you
confirm every
transmitter.
If 0 (No) is entered, the
XMIT TO CONFIRM
prompt is automatically
skipped.
This option is ignored if
programming wired zones
only.