HLP-C
+
Inverters
of load. Otherwise it is extremely easy to cause overcurrent
protection.
C096 Restart after Instantaneous Stop
Set Range
:
0~1
Factory Setting
:
0
0
:
Invalid, i.e. the inverter will not restart after an instantaneous stop.
1
:
Speed search Start. Refer to C094.
C097 Allowable Power-off Time
Set Range
:
0.1~5.0S
Unit
:
0.1S Factory Setting
:
0.5
This parameter is set for the maximum allowable power off
time. If exceeding the set time the inverter will continue to stop
input after power on. To execute the restart it needs to follow
the general starting procedures.
*Attention
:
When using this function special attention should
be paid to the safety. During the process of instantaneous power
off and power on the inverter may restart. It is easy to produce
danger. Be careful to use this function.
C098 Number of Abnormal Restart
Set Range
:
00~10
Unit
:
1
Factory Setting
:
00
After the abnormal conditions (such as overcurrent, overvoltage)
happen the invrter will automatically reset and restart. If the
starting mode is set for general mode it will start according to
the general mode. If it is set for speed search start it will start in
the speed search mode. After start it will restore the set number
again if there is not anything unusual happened within 60
seconds. If there is any error and it reaches the set number the
inverter will not have input. It can only be started after reset. If
C098 is set to 0 the inverter will not carry out the functions of
automatic reset and restart.
C099 Auto Voltage Regulation
Set Range
:
0~1
Factory Setting
:
1
0
:
Invalid
1
:
Valid