HLP-C
+
Inverters
Stall prevention level
during running
Output
frequency
C082 Stall Prevention Level During Deceleration
Set Range
:
0~200%
Unit
:
1
Factory Setting
:
180
100% current is the rated current of the motor. When this
parameter is set to 0, the stall prevention function is invalid.
Related introduction refer to C079.
When this parameter is set to 0, the stall prevention function is
invalid.
C083 Overtorque Detect Level
Set Range
:
0~200%
Unit
:
1%
Factory Setting
:
0
When the output current exceeds the over torque detection level
and also exceeds half of the set over torque detection time (factory
setting: 1.0s), the over torque detection will begin to indicate,
and the corresponding multi-function contact will act. When
it exceeds the set time value, the inverter will turn into self-
protection. But when this parameter is set to 0, the over torque
detection will be invalid
C084 OverTorque Detect Time
Set Range
:
0.1~20.0S
Unit
:
0.1S Factory Setting
:
1.0
When the inverter detects that the output current has exceeded
the motor current set value, the inverter begins to calculate
the over torque time. When the over torque time has exceeded
half of the over torque detection time, the corresponding multi-
function output contact will act, the over torque alarm will be
produced, while the inverter will continue running. When the
over torque time has exceeded the set detection time (set by