HLP-C
+
Inverters
This parameter sets the highest operating frequency of the
inverter.
The settings of C006, C007, C008 and C009 are related to the
setting value of C125. When C125 is set as 0, the factory setting
is the first V/F curve, while C125 is set as 1, the factory setting
is the second V/F curve. When restoring the factory setting the
memorized contents are as above.
Note: means uncertain values or various setting values.
C011 Frequency Lower Limit
Set Range
:
0.0~600.0
Unit
:
0.1Hz Factory Setting
:
0.00
This is set for preventing workers from false operation, avoiding
overheat or some other mechanical faults, which might be caused
due to the too low running frequency. When the setup frequency
is below the lower limit the inverter is running at frequency
lower limit.
This set value is limited by frequency upper limit.
C012 Control Mode
Set Range
:
0~2
Unit
:
1
Factory Setting
:
0
0
:
Control by the digital operator. The running command is
given through the digital operator.
1
:
Control by external terminals. The running command is given
through external terminals (multi-function input terminals).
2
:
Control by the communication ports. The running command
is given through communication ports.
C013 Running Frequency
Select Set Range
:
0~2
Unit
:
1
Factory Setting
:
0
0
:
Set by digital operator.
The running frequency is given through the digital operator.
1
:
Set by potentiometer.
The running frequency is controlled by the analog signal
through external terminals or potentiometer of the panel. Relate
to CNI state.