HLP-C
+
Inverters
C026 PLC Rotation Direction
Set Range:0~255
Factory Setting:0
This parameter is only valid when C024 is set to 4.
The setting of this parameter determines the rotation directions
of each frequency step of C035~C041 and C000 in the pattern
run. The setting method is as follows:
The rotation direction is set first in the binary bit mode, and then
converted to a decimal value for the setting of this parameter.
For instance:
bit 0-7
7
6
5
4
3
2
1
0
0
1
0
0
1
0
1
0
0:For 1:Rev
Main Speed (C000)For
Step 1 (C035) Rev
Step 2 (C036) For
Step 3 (C037) Rev
Step 4 (C038) For
Step 5 (C039) For
Step 6 (C040) Rev
Step 7 (C041) For
The parameter value 01001010 is converted to a decimal value:
1×2
6
+1×2
3
+1×2
1
=64+8+2=74
Then C026=74
C027 PLC Accel. / Decel. Time 1
Set Range:0~255
Factory Setting:0
This parameter is only valid when C024 is set to 4.
Thisparameter is set to determine the accel/decel time values
of Step 1~4 of the internally controlled multi-speed. Its setting
method is as follows: