- 0 -
HLP-C
+
Inverters
PID closed-loop control is valid only when the multi-function
inputs PID are open.
C106 PID Constant Target Value
Set Range
:
0~1
Unit
:
1
Factory Setting
:
0
The selection of target value can be set through the selection
of the panel or external analog quantity. The external analog
quantity is 0~10V signal or control of the potentiometer.
When C106=0,the target value of PID is set by C105.
When C106=1,the target value of PID is set by external analog
signal 0-10V(corresponding 0-100%), the setting of C105 is
invalid.
It should be noticed that in using PID control PID is only valid
when C013 is set to 0.
C107 PID Upper Limit
Set Range
:
0~100%
Unit
:
1 Factory Setting
:
100%
When PID feedback value is more than the set value of C107 the
corresponding multi-output terminal will act and the machine
will not stop.
C108 PID Lower Limit
Set Range
:
0~100%
Unit
:
1
Factory Setting
:
0
When PID feedback value is less than the set value of C108 the
corresponding multi-output terminal will act and the machine
will not stop.
C109 Communication Addresses
Set Range
:
00~250
Unit
:
1
Factory Setting
:
00
When the inverter is set to have RS-485 Communication
interface control, each of the inverters will be set for its
individual identification number through C109.
00
:
No communication function
01~250
:
Individual identification number for the inverters