HLP-C
+
Inverters
(1) Determine each accel/decel time in in the binary 2 bit mode
Bit1
Bit2
Accel/Decel Time
0
0
Accel/Decel Time 1: C001, C002
0
1
Accel/Decel Time 2: C029, C030
1
0
Accel/Decel Time3: C031, C032
1
1
Accel/Decel Time 4: C033, C034
(2) Determine the accel/decel time of each speed step in in the
binary 8 bit mode
Speed No. 4 Speed No. 3 Speed No. 2
Speed No. 1
t4
t3
t2
t1
0
1
1
0
0
0
1
1
t1 Select Accel. Time 4 t2 Select Accel. Time 1
t3 Select Accel. Time 3 t4 Select Accel. Time 2
The setting value: 1×2
0
+1×2
1
+1×2
5
+1×2
6
=99, So C027is set to 99.
Attach:2
0
=1+2
1
=2, 2
2
=4, 2
3
=8, 2
4
=16, 2
5
=32, 2
6
=64
C028 PLC Accel. / Decel. Time 2
Set Range:0~255
Factory Setting:0
Thisparameter is set to determine the accel/decel time of Step
5~8 of the internally controlled multi-speed. Its setting method
is the same as C026 and C027. Details refer to the description of
C027.
C029 Accel. Time 2
Set Range:0.1~6500S
Unit:0.1S
Factory Setting:10.0
C030 Decel. Time 2
Set Range:0.1~6500S
Unit:0.1S
Factory Setting:10.0
C031 Accel. Time 3
Set Range
:
0.1~6500S
Unit
:
0.1S Factory Setting
:
50.0
C032 Decel. Time 3
Set Range:0.1~6500S
Unit:0.1S
Factory Setting:50.0