HLP-C
+
Inverters
Note:
⑴
The function of UP and DOWN is only valid when the
operation of Operator is delected for the source of the running
frequency, i.e. C013=0.
⑵
When UP is closed the inverter’s frequency will increment.
⑶
When DOWN is closed the inverter’s frequency will
decrement.
⑷
When both UP and DOWNare closed at the same time the
frequency will neither increase nor decrease. It is regaded as
invalid.
⑸
When the frequency reaches the max. operation frequency it
will not increase.
⑹
When the frequency reaches the min.. frequency or its lowe
limit, it will not decrease.
⑺
It has the function of memory, including the memory for
power-off. (Setting C60=1)
⑻
When adopting the function of UP and DOWN, its up and
down speed rate is determined by the present Accel/Decel Tiem.
⑼
When keeping pressing UP or DOWN
,
the frequency will
increase or decrease rapidly.
⑽
The function of UP and DOWN is valid in operation. The
frequency cannot be changed during wait.
待机
F. Description of Multi-speed 1, 2 and 3 Functions
They are only valid when C024 is set to 2. Details refer to C024.
G. Description of Counter Function
t
2
t
1
Value reach
Value reset
Note:
⑴
The signal width triggered should not be lower than 2msec