HLP-C
+
Inverters
time of jog frequency is set by C023. Jog stopping mode is the
same as the normal run stopping mode, which can be set by C15.
This function is only valid at stop condition. It is invalid at
running. When C012 is set to 1, it is valid.
C023 Jog Accel/Decel Time
Set Range
:
0.1~25.0
Unit
:
0.1
Factory Setting
:
1.0
The set value of Jog Accel/Decel Time responds to Accel/Decel
Time of 0~50Hz.
C024 PLC Operation
Set Range
:
0~5
Factory Setting
:
0
0
:
Normal operation, i.e. the inventer is running by the normal
control method.
1
:
Excternal control 4- Speed Steps
In the excternal control 4-Speed Steps the disturbance function
can be used at intermediate speed. Then C41 (Frequency 8) is
the disturbance amplitude. If it is equal to zero this function is
invalid. C042 Time 1 and C043 Time 2 are disturbance time.
Detail descriptions refer to the function description and diagram
of three terminals of high, intermediate and low speed C050
~
C055.
2
:
Excternal control multi- speeds