HLP-C
+
Inverters
the inverter will operate according to each parameter, but it will
stop first and then restart at the change of each stage. It will stop
automatically after running for onw week. Only with another
running cammand given the inverter can restart.
(2) The frequencies of each speed step are set by C000,
C035~C041.
(3) The running times of each speed step are set by C042~C049.
(4) The running direction is set by C026.
3:Auto running (Stop for intervention) and recycling operation.
Step finished
Command
Pattern finished
Command
Note:
(1) After the auto pattern run command is given the inverter will
run according to the parameters, but at every change of step it
will stop first and then start again. It will continue and stop until
the OFF command for auto run is given.
(2) When each step is finished the corresponding multi-function
output contac will act.
(3) When each pattern run is finished the corresponding multi-
function output contac will act.
(4) The width of output pulse is 20 ms.
(5) When running again after power off all the actions will be
started from the beginning and the previous states will not be
memorized.