return reg_crc;
}
C120 Parameter lock
Set Range
:
0~1
Unit
:
1
Factory Setting
:
0
0
:
Invalid. The parameter can be set.
1
:
Valid, i.e. parameter lock. Except this parameter and C000
other parameterscan bechanged.
This parameter can be used to prevent any wrong setting of
other values by non maitenance persons.
C121 Display Contents
Set Range
:
0~255
Factory Setting
:
00
DC Voltage: 1
Temperature: 2
Counter: 4
Feedback Value: 8
RPM: 16
Normally we can see directly output frequency, set frequency,
output current,output voltage, but temperatue, DC voltage,
counter, PID feedback and revolution speed can only be
monitored and displayed in sequence through switching keys
after the setting of C121.
Set the corresponding code for C121. If it often displays the
content of more than tow items set the corresponding code for
C121 again.
For example: when asking for displaying the temperature and
revolution, then C121=2+16=18
,
just set C121to 18.
C122 Inverter Model
Factory Setting
:
*
Factory Setting. It can be monitored, but not set.
C123 Rated Inverter Voltage
Factory Setting
:
*
Factory Setting. Depending on the model. It can be monitored, but not set.