HLP-C
+
Inverters
01
:
Run: It can be combined with other terminals to combine
various control methods.
02
:
Forward rotation
03
:
Reverse rotation
04
:
Stop
05
:
For/Rev switching
06
:
Jog07
:
Jog For rotation
08
:
Jog Rev rotation
09
:
Emergency Stop: It can receive externally coming
emergency stop or other fault signals. When the terminal
is closed, the inverter will stop output and come to a stop
at free running.
10
:
Reset: This terminal can be used to reset after the fault is
removed.
12
:
Overheat of radiator or motor: This contact can be used
to detect overheat of the radiator or motor to protect the
motor and inverter.
13
:
Externally Controlled Timer 1 start: When the contact is
closed, the timer will start and begin to count time. When
the timer reaches the point the responding multi-inputs
will act.
14
:
Externally Controlled Timer 2 start
17
:
High Speed: High, intermediate and low speed can
compose three kinds of different operation patterns.
18
:
Intermediate Speed: In the three terminals the high-end
signal has priority.
19
:
Low Speed: Low, intermediate and high speed are
determined by Frequency 2, 3, 4.
20
:
Multi-speed 1
21
:
Multi-speed 2: Multi-speed 1, 2, 3 can compose 7-Steps.
22
:
Multi-speed 3
23
:
Acel/Decel Select 1: This terminal can be used to selcect
the acel/decel time of the inverter.
24
:
Acel/Decel Select 2: 4 kinds of Acel/Decel are available
for choice.
25
:
UP function: When this terminal switch acts the
frequency of the inverter will increase or decrease. When
the terminal switch is hold the frequency will rapidly