80
Setting
value
Functionalities
Description
41
Motor selection terminal 1
2 sets of motor parameters can be switched through the 2
states of terminals, see table 3 for details.
42
Reserve
Reserve
43
PID parameter switching
When the PID parameter switching condition is X terminal (FA -
18 = 1), when the terminal is invalid, the PID parameters are FA
- 05 ~ FA - 07; When the terminal is valid, FA - 15 ~ FA - 17 will
be used.
44
User - defined fault 1
When user-defined faults 1 and 2 are valid, the frequency
inverter alarms UEF1 and UEF2 respectively.
45
User - defined fault 2
46
Speed control / torque control
switching
It causes the inverter to switch between torque control and
speed control modes. When this terminal is invalid, the inverter
operates in the mode defined by F7 - 00 (speed / torque control
mode), and when this terminal is valid, it switches to another
mode. During operation, switching can be carried out through
terminals, which will take effect immediately after switching
47
Emergency stop
When the terminal is valid, the frequency inverter stops at the
fastest speed, and the current is at the upper limit set during
the stop. This function is used to meet the requirement that the
frequency inverter needs to be shut down as soon as possible
when the system is in an emergency.
48
External parking terminal 2
Under any control mode (panel control, terminal control, and
communication control), this terminal can be used to slow
down and stop the frequency inverter. The deceleration time at
this time is fixed at deceleration time 4.
49
Deceleration DC brake
When this terminal is active, the frequency inverter will first
slow down to the stop DC brake starting frequency and then
switch to the DC brake state.
50
This run time is cleared
When this terminal is valid, the timing time of this operation of
the frequency inverter is cleared. This function needs to be
used in conjunction with the timing operation (F8 - 04) and the
arrival of this operation time (F8 - 07).
51
Two - wire / three-wire switching
For switching between two-wire and three-wire control. If F5 -
11 is two-wire type 1, switch to three-wire type 1 when the
terminal function is valid. And so on.
52
Prohibition of reversal
This terminal is valid, and frequency inverter reversal is
prohibited. Same function as F0 - 04.
Four multi-segment command terminals can be combined into 16 States, each of which corresponds to 16
command settings. Specific as shown in table 1:
Attached table 1 multi-paragraph instruction function description
K4
K3
K2
K1
Command setting Corresponding
parameter
OFF
OFF
OFF
OFF
Multi - segment
instruction 0
FC-00
OFF
OFF
OFF
ON
Multi - segment
instruction 1
FC-01
OFF
OFF
ON
OFF
Multi - segment
instruction 2
FC-02
OFF
OFF
ON
ON
Multi - segment
instruction 3
FC-03
OFF
ON
OFF
OFF
Multi - segment
instruction 4
FC-04
Содержание HV480 Series
Страница 1: ...HV610 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 12: ...8 2 2 3 Frequency inverter control loop terminal description ...
Страница 13: ...9 ...
Страница 166: ...162 Appendix II Plastic shell dimensions and mounting dimensions Fig 1 R75G3 2R2G3 Fig 2 004G3 7R5G3 ...
Страница 167: ...163 Appendix III dimensions and mounting dimensions of sheet metal machines Fig 3 011G3 200G3 Fig 4 185G3 560G3 ...