Figure 5 - 20 linear acceleration and deceleration
1: S curve acceleration and deceleration
The output frequency increases or decreases according to the S curve. The S curve is used in places that
require gentle start-up or shutdown, such as electric ladders and conveyor belts. The function codes F6 - 24 and F6 -
25 define the time ratios of the start and end segments of the S - curve acceleration and deceleration respectively.
Figure 5 - 21 S curve acceleration and deceleration
F6 - 24 S curve start period time proportion
0%
~
0.0%
~
(100.0%-F6-25)
【
30%
】
F6 - 25 S curve end period time proportion
0%
~
0.0%
~
(100.0%-F6-26)
【
30%
】
The function codes F6 - 24 and F6 - 25 respectively define the time ratio between the start and end periods of
the S curve acceleration and deceleration A and the two function codes shall meet the following requirements: F6-24
+ F6-25 ≤ 100.0%
Time
Frequency
Acceleration time
Deceleration time
Time
Frequency
Acceleration time
Deceleration time