74
The FMP terminal output pulse frequency ranges from 0.01 kHz to F4 - 09 (FMP output the maximum frequency),
and F4 - 09 can be set between 0.01 kHz and 100.00 kHz.
The analog outputs AO1 and AO2 range from 0V to 10V, or 0 mA to 20 mA.
The calibration relationship between the range of pulse output or analog output and corresponding functions is
shown in the following table:
Setting
value
Functionalities
Description
0
Running frequency
0 ~ maximum output frequency
1
Set frequency
0 ~ maximum output frequency
2
Output current
0 ~ 2 times rated current of motor
3
Output torque ( absolute value )
0 ~ 2 times rated torque of motor
4
Output power
0 ~ 2 times rated power
5
Output voltage
0 ~ 1.2 times rated voltage of frequency inverter
6
PULSE pulse input
0.01kHz
~
100.00kHz
7
AI1
0V
~
10V
8
AI2
0V
~
10V
(
or 0
~
20mA
)
9
AI3
0V
~
10V
10
Length
0 ~ maximum set length
11
count value
0 ~ maximum count value
12
Communication settings
0.0% - 100.0%
13
Motor rotational speed
Rotational speed corresponding to 0 ~ maximum output
frequency
14
Output current
0.0A
~
1000.0A
15
Output voltage
When 0.0v to 1000.0v
16
Output torque ( actual value )
- 2x motor rated torque ~ 2x motor rated torque
F4 - 09 FMP output maximum frequency
0.01kHz
~
100.00kHz [50.00Khz]
F4 - 10 AO1 zero offset coefficient
-100.0%
~
+100.0% [0.0%]
F4 - 11 AO1 gain
-10.00
~
+10.00 [1.00]
F4 - 12 AO2 zero offset coefficient
-100.0%
~
+100.0% [0.0%]
F4 - 13 AO2 gain
-10.00
~
+10.00 [1.00]
Содержание HV480 Series
Страница 1: ...HV610 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 12: ...8 2 2 3 Frequency inverter control loop terminal description ...
Страница 13: ...9 ...
Страница 166: ...162 Appendix II Plastic shell dimensions and mounting dimensions Fig 1 R75G3 2R2G3 Fig 2 004G3 7R5G3 ...
Страница 167: ...163 Appendix III dimensions and mounting dimensions of sheet metal machines Fig 3 011G3 200G3 Fig 4 185G3 560G3 ...