155
Common monitoring address (read - only)
Communication address
Address description
1001H
Operating frequency ( unit: 0.01 Hz )
1002H
Bus voltage ( unit: 1v )
1003H
Output voltage ( unit: 1v )
1004H
Output current ( unit: 1v )
1005H
Output power
( unit: 0.1 kw )
1006H
Output torque ( unit: 0.1 % )
1007H
running speed
1008H
X input terminal status
1009H
Output terminal status
100AH
AI1 voltage ( unit: 0.01 v )
100BH
AI2 voltage ( unit: 0.01 v )
100CH
AI3 voltage ( unit: 0.01 v )
100FH
loading speed
1013H
Feedback frequency ( unit: 0.1 Hz )
101EH
Encoder feedback frequency ( unit: 0.01 Hz )
Communication control special register address 2000 H (write only)
value
Description
1
Forward running
2
Reverse operation
3
Forward jog
4
Reverse inching
5
Free stop
6
Deceleration shutdown
7
Fault reset
The control mode is F0 -02 = 2. By writing the corresponding data word into the communication control
command word 2000 H, the operation / stop / jog / reset of the frequency inverter can be controlled.