14
This is one of the most common wiring methods. If an external power supply is used, the short connector
b 24V and OP and the short connector between COM and CME must be removed. The positive electrode of
the external power supply is connected to OP and the negative electrode of the external power supply is connected
to CME.
Multiple frequency inverters digital input and connection leakage type connection mode
Multiple frequency inverters digital input terminals cannot be connected and used, otherwise it may cause
incorrect operation of the input terminals. If it is needed that the input terminals of different frequency inverters are
connected in parallel, the diode is connected in series at the X terminal and the wiring is as shown above and the
diode needs to meet IF
>
10mA
,
UF
<
1V
Source type wiring mode
This wiring mode must remove the short connectors of 24v and OP, and c 24v to the common terminal
of the external controller together, COM and OP are connected together at the same time. If an external power
supply is used, the short connector between COM and CME must also be removed.
Signal
Signal
External controller
External controller
Frequency 2 inverter control panel
Frequency 1 inverter control panel
Frequency inverter control panel
Содержание HV480 Series
Страница 1: ...HV610 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 12: ...8 2 2 3 Frequency inverter control loop terminal description ...
Страница 13: ...9 ...
Страница 166: ...162 Appendix II Plastic shell dimensions and mounting dimensions Fig 1 R75G3 2R2G3 Fig 2 004G3 7R5G3 ...
Страница 167: ...163 Appendix III dimensions and mounting dimensions of sheet metal machines Fig 3 011G3 200G3 Fig 4 185G3 560G3 ...