142
Rated voltage of
frequency inverter
(V) / phase number
Motor power
(
kW
)
Braking electrical
resistance value
(
Ω
)
Braking electric
resistance power
(
kW
)
The braking electrical
resistance is the smallest
Value ( Ω )
Note
380V/3Φ
0.75
800
0.08
>400
Built - in brake unit
380V/3Φ
1.5
400
0.16
>220
Built - in brake unit
380V/3Φ
2.2
250
0.24
>200
Built - in brake unit
380V/3Φ
4.0
150
0.4
>130
Built - in brake unit
380V/3Φ
5.5
100
0.6
>90
Built - in brake unit
380V/3Φ
7.5
75
0.8
>65
Built - in brake unit
380V/3Φ
11
50
1.0
>45
Built - in brake unit
380V/3Φ
15
40
1.5
>32
Built - in brake unit
380V/3Φ
18.5
30
3.0
>25
Built - in brake unit
380V/3Φ
22
30
3.0
>22
Built - in brake unit
380V/3Φ
30
20
4.0
>16
External brake unit
380V/3Φ
37
16
6.0
>13
External brake unit
380V/3Φ
45
13.6
6.0
>11
External brake unit
380V/3Φ
55
20/2
8.0
>9
External brake unit
380V/3Φ
75
13.6/2
12
>6.5
External brake unit
380V/3Φ
93
20/3
12
>5.5
External brake unit
380V/3Φ
110
20/3
12
>4.5
External brake unit
380V/3Φ
132
20/4
16
>4.5
External brake unit
380V/3Φ
160
13.6/4
18
>6.5/2
External brake unit
380V/3Φ
185
13.6/4
20
>3
External brake unit
380V/3Φ
200
13.6/4
24
>2.5
External brake unit
380V/3Φ
220
13.6/5
30
>2
External brake unit
380V/3Φ
250
13.6/5
30
>2
External brake unit
380V/3Φ
280
13.6/6
36
>1.8
External brake unit
380V/3Φ
315
13.6/6
36
>1.8
External brake unit
380V/3Φ
355
-
-
-
If you need brake,
please contact the
manufacturer.
380V/3Φ
400
-
-
-
380V/3Φ
450
-
-
-
380V/3Φ
500
-
-
-
380V/3Φ
560
-
-
-
3) Regarding the brake unit
No regenerative braking function is built in the 30kw G series type of frequency inverter and above specifications.
When braking energy is needed, an energy consumption braking unit should be added. It should be noted when
ordering. The brake unit shall be connected to the Θ and
⊕
terminals of the frequency inverter, and the brake
resistor shall be connected to the external brake unit. The regenerative braking function is necessary when the
braking torque of the machine itself cannot meet the application requirements, especially when it is under large
inertia load, frequently broken or quickly stopped.
In situations requiring higher fast braking, even if an energy-consuming braking device is installed, the user is
advised to use a feedback braking unit.
8.2.6 External DC reactor
The series of frequency inverters are all externally connected with DC reactors. If necessary, please consult the
distributor or the factory directly for specific specifications.
8.2.7 Radio noise filter
The product is designed to meet the requirements of national standard GB/T12668.3 in terms of electromagnetic
compatibility (that is, EMC refers to the ability of electrical equipment to operate in an electromagnetic interference
environment, not to interfere with the electromagnetic environment, and to realize its functions stably). Frequency
inverters need to meet the requirements of both electromagnetic interference and anti-electromagnetic interference.
Electromagnetic interference mainly refers to radiation interference, conduction interference and harmonic
Содержание HV480 Series
Страница 1: ...HV610 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 12: ...8 2 2 3 Frequency inverter control loop terminal description ...
Страница 13: ...9 ...
Страница 166: ...162 Appendix II Plastic shell dimensions and mounting dimensions Fig 1 R75G3 2R2G3 Fig 2 004G3 7R5G3 ...
Страница 167: ...163 Appendix III dimensions and mounting dimensions of sheet metal machines Fig 3 011G3 200G3 Fig 4 185G3 560G3 ...