38
Function
code
Name
Setting range
Factory
value
Communica
tion address
F8-22
Instantaneous power
failure action judges OFF
voltage
60.0 % ~ 100.0 % ( standard bus voltage )
80.0%
F816H
F8-23
Pendulum frequency
setting mode
0: relative to center frequency
1: relative to maximum frequency
0
F817H
F8-24
Swing amplitude
0.0% ~ 100.0%
0.0%
F818H
F8-25
Amplitude of sudden
jump frequency
0.0% ~ 50.0%
0.0%
F819H
F8-26
Frequency swing period 0.1s
~
3000.0s
10.0s
F81AH
F8-27
Rise time of triangular
wave of pendulum
frequency
0.1% ~ 100.0%
50.0%
F81BH
F8-28
Set length
0m
~
65535m
1000m
F81CH
F8-29
Actual length
0m
~
65535m
0m
F81DH
F8-30
Number of pulses per
meter
0.1
~
6553.5
100.0
F81EH
F8-31
Set the count value
1
~
65535
1000
F81FH
F8-32
Specify count value
1
~
65535
1000
F820H
F9 group failure and protection
F9-00
Motor overload
protection selection
0: prohibited
1: allowed
1
F900H
F9-01
Motor overload
protection gain
0.20
~
10.00
1.00
F901H
F9-02
Motor overload early
warning coefficient
50% ~ 100%
80%
F902H
F9-03
over voltage stall gain
0
~
100
30
F903H
F9-04
over voltage stall
protection voltage
200.0V ~ 2000.0V
760.0V
F904H
F9-05
Over - loss rate gain
0
~
100
20
F905H
F9-06
Over current protection
current
100% ~ 200%
150%
F906H
F9-07
Selection of short circuit
protection between
power-on and ground
0: invalid
1: valid
1
F907H
F9-08
Does the under voltage
fault reset automatically
0: auto reset
1: not automatically reset
0
F908H
F9-09
Number of automatic
fault resets
0
~
20
0
F909H
F9-10
Fault DO action selection
during automatic fault
reset period
0: no action
1: action
0
F90AH
F9-11
Time between automatic
fault reset
0.1s
~
100.0s
1.0s
F90BH
F9-12
Input phase missing \
contactor suction
protection selection
Bits: input phase loss protection selection
10 bits: contactor pull-in protection selection
0: prohibited
1: allowed
11
F90CH
F9-13
Output phase - missing
protection selection
0: prohibited
1: allowed
1
F90DH
Содержание HV480 Series
Страница 1: ...HV610 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 12: ...8 2 2 3 Frequency inverter control loop terminal description ...
Страница 13: ...9 ...
Страница 166: ...162 Appendix II Plastic shell dimensions and mounting dimensions Fig 1 R75G3 2R2G3 Fig 2 004G3 7R5G3 ...
Страница 167: ...163 Appendix III dimensions and mounting dimensions of sheet metal machines Fig 3 011G3 200G3 Fig 4 185G3 560G3 ...