120
Figure 5 - 34 AI calibration method diagram
Measured actual measured AI1
voltage value is recorded as v1
Given AI2 voltage signal (2v or so)
Given AI3 voltage signal (2v or so)
Given AI1 voltage signal (2v or so)
Measured actual measured AI2
voltage value is recorded as v1
Measured actual measured AI3
voltage value is recorded as v1
View U0 - 21 display value record as
u1
View U0 - 22 display value record as
u1
View U0 - 23 display value record as
u1
Given AI1 voltage signal (8v or so)
Given AI2 voltage signal (8v or so)
Given AI3 voltage signal (8v or so)
Measured actual measured AI1
voltage value is recorded as v2
Measured actual measured AI2
voltage value is recorded as v2
Measured actual measured AI3
voltage value is recorded as v2
View U0 - 21 display value record as
U2
View U0 - 22 display value record as
U2
View U0 - 23 display value record as
U2
V1 input P2 – 00
u1 input P2 – 01
v2 input P2 – 02
u2 input P2 - 03
V1 input P2 – 04
u1 input P2 – 05
v2 input P2 – 06
u2 input P2 - 07
V1 input P2 – 08
u1 input P2 – 09
v2 input P2 – 10
u2 input P2 - 11
AI1 calibration completed
AI2 calibration completed
AI3 calibration completed
Содержание HV480 Series
Страница 1: ...HV610 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 12: ...8 2 2 3 Frequency inverter control loop terminal description ...
Страница 13: ...9 ...
Страница 166: ...162 Appendix II Plastic shell dimensions and mounting dimensions Fig 1 R75G3 2R2G3 Fig 2 004G3 7R5G3 ...
Страница 167: ...163 Appendix III dimensions and mounting dimensions of sheet metal machines Fig 3 011G3 200G3 Fig 4 185G3 560G3 ...