85
F5 - 20 X3 delay time
0.0s
~
3600.0s [0.00S]
Used to set the delay time for the change of X terminal state by the frequency inverter at present, only X1, X2,
X3 have the function of setting the delay time.
F5 - 21 X terminal active mode selection 1
00000
~
11111 [00000]
Bit: x1 terminal logic set to
0: positive logic
1. Inverse logic
10 bits: X2 terminal valid state setting (0 ~ 1, ditto)
100 bits: X3 terminal valid state setting (0 ~ 1, ditto)
1000 bits: X4 terminal valid state setting (0 ~ 1, ditto)
10,000 bits: X5 terminal valid state setting (0 ~ 1, ditto)
When positive logic is selected, the corresponding X terminal is valid when connected to com, and
disconnection is invalid.
If it is selected as anti-logic valid, the corresponding X terminal will not be valid if it is connected to com, and the
disconnection will be valid.
F5 - 22 X terminal active mode selection 2
00000
~
11111 [00000]
Bit: X6 terminal logic set to 0: positive logic
1: inverse logic
10 bits: x7 terminal active state setting (0 ~ 1, same as above)
When positive logic is selected, the corresponding X terminal is valid when connected to com, and
disconnection is invalid.
If it is selected as anti-logic valid, the corresponding X terminal will not be valid if it is connected to com, and the
disconnection will be valid.
F5 - 24 AI curve 1 min input
0.00V
~
F5-26 [0.00V]
F5 - 25 AI curve 1 minimum input corresponding settings -100.0%
~
100.0% [0.0%]
F5 - 26 AI curve 1 maximum input
F5-24
~
10.00V [10.00V]
F5 - 27 AI curve 1 maximum input corresponding settings -100.0%
~
100.0% [100.0%]
F5 - 28 AI1 filtering time
0.00s
~
10.00s [0.10s]
The above function code is used to set the relationship between the analog input voltage and the set value it
represents.
When the voltage of analog input is greater than the set “maximum input" (F5 - 26), the analog voltage is calculated
according to “maximum input". Similarly, when the analog input voltage is less than the set " minimum input" ( F5 -
24 ), it is calculated as the minimum input or 0.0 % based on the setting of " AI is lower than the minimum input
setting selection" ( F5 - 40 ).
When the analog input is a current input, 1ma current is equivalent to 0.5v voltage.
AI1 input filtering time is used to set the software filtering time of AI1. When the analog quantity in the field is
easily interfered, please increase the filtering time to stabilize the detected analog quantity. However, the larger the
filtering time is, the slower the response speed to the analog quantity detection will be. How to set it needs to be
weighed according to the actual application situation
In different applications, the meaning of the nominal value corresponding to 100.0 % set by simulation is
different. Please refer to the description of each application section for details.
The following illustrations show two typical settings:
Содержание HV480 Series
Страница 1: ...HV610 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 12: ...8 2 2 3 Frequency inverter control loop terminal description ...
Страница 13: ...9 ...
Страница 166: ...162 Appendix II Plastic shell dimensions and mounting dimensions Fig 1 R75G3 2R2G3 Fig 2 004G3 7R5G3 ...
Страница 167: ...163 Appendix III dimensions and mounting dimensions of sheet metal machines Fig 3 011G3 200G3 Fig 4 185G3 560G3 ...