Chapter 8 List of Data Settings
8 - 13
Code
Function name
Monitored data or setting
Default
Setting
during
operation
(allowed
or not)
Change
during
operation
(allowed
or not)
Page
_FF
C
ontr
o
l co
nst
a
nt
s
H001 Auto-tuning
Setting
00 (disabling auto-tuning), 01 (auto-tuning without rotation),
02 (auto-tuning with rotation)
00
¯
¯
4-86
H002
Motor data selection, 1st motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
¯
¯
H202
Motor data selection, 2nd motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
¯
¯
H003
Motor capacity, 1st motor
0.20 to 90.00 (kW) <0.20 to 160. (kW) >
Factory setting
¯
¯
H203
Motor capacity, 2nd motor
0.20 to 90.00 (kW) <0.20 to 160. (kW) >
Factory setting
¯
¯
H004
Motor poles setting, 1st motor
2, 4, 6, 8, 10 (poles)
4
¯
¯
H204
Motor poles setting, 2nd motor
2, 4, 6, 8, 10 (poles)
4
¯
¯
H005
Motor speed constant, 1st motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590
{
{
4-89
H205
Motor speed constant, 2nd motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590
{
{
H006
Motor stabilization constant, 1st motor 0. to 255.
100.
{
{
4-82
H206
Motor stabilization constant,
2nd motor
0. to 255.
100.
{
{
H306
Motor stabilization constant,
3rd motor
0. to 255.
100.
{
{
H020
Motor constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
4-91
H220
Motor constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
H021
Motor constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
H221
Motor constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
H022
Motor constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor capacity
¯
¯
H222
Motor constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor capacity
¯
¯
H023
Motor constant Io
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor capacity
¯
¯
H223
Motor constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor capacity
¯
¯
H024
Motor constant J
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on
motor capacity
¯
¯
H224
Motor constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on
motor capacity
¯
¯
H030
Auto constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
4-86
H230
Auto constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
H031
Auto constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
H231
Auto constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on
motor capacity
¯
¯
H032
Auto constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor capacity
¯
¯
H232
Auto constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on
motor capacity
¯
¯
H033
Auto constant Io, 1st motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor capacity
¯
¯
H233
Auto constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on
motor capacity
¯
¯
H034
Auto constant J, 1st motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on
motor capacity
¯
¯
H234
Auto constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on
motor capacity
¯
¯
Co
n
tro
l con
st
a
nt
s
H050
PI proportional gain for 1st motor
0.0 to 999.9, 1000.
100.0
{
{
4-60
H250
PI proportional gain for 2nd motor
0.0 to 999.9, 1000.
100.0
{
{
H051
PI integral gain for 1st motor
0.0 to 999.9, 1000.
100.0
{
{
H251
PI integral gain for 2nd motor
0.0 to 999.9, 1000.
100.0
{
{
H052
P proportional gain setting for 1st
motor
0.01 to 10.00
1.00
{
{
H252
P proportional gain setting for 2nd
motor
0.01 to 10.00
1.00
{
{
H070
Terminal selection PI proportional
gain setting
0.0 to 999.9, 1000.
100.0
{
{
4-59
H071
Terminal selection PI integral gain
setting
0.0 to 999.9, 1000.
100.0
{
{
H072
Terminal selection P proportional gain
setting
0.00 to 10.00
1.00
{
{
H073
Gain switching time
0. to 9999. (ms)
100.
{
{
(Note)<>indicate the setting range of 90 to 160kW
Содержание L700 Series
Страница 16: ... Memo ...
Страница 20: ... Memo ...
Страница 22: ... Memo ...
Страница 46: ... Memo ...
Страница 60: ... Memo ...
Страница 62: ... Memo ...
Страница 212: ... Memo ...
Страница 222: ... Memo ...
Страница 224: ... Memo ...
Страница 232: ... Memo ...
Страница 237: ...Chapter 7 Specifications 7 5 L700 300 LFF HFF L700 450 550 LFF HFF 750 HFF 5 Cable hole φ25 5 Cable hole φ41 ...
Страница 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Страница 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Страница 240: ... Memo ...
Страница 242: ... Memo ...
Страница 258: ... Memo ...