Chapter 4 Explanation of Functions
4 - 131
Register
No.
Function name
Function code
R/W
Monitoring and setting items Data resolution
Register
No.
1236h (Reserved)
-
- Inaccessible
-
1237h (Reserved)
-
- Inaccessible
-
1238h
Jog frequency setting
A038
R/W "Start frequency" to 999
0.01 [Hz]
1239h
Jog stop mode
A039
R/W
0 (free-running after jogging stops [disabled during
operation])
1 (deceleration and stop after jogging stops [disabled
during operation])
2 (DC braking after jogging stops [disabled during
operation])
3 (free-running after jogging stops [enabled during
operation])
4 (deceleration and stop after jogging stops [enabled
during operation])
5 (DC braking after jogging stops [enabled during
operation])
-
123Ah (Reserved)
-
-
-
123Bh
Torque boost method
selection
A041
R/W 0 (manual torque boost), 1 (automatic torque boost)
-
123Ch Manual torque boost value
A042
R/W 0 to 200
0.1 [%]
123Dh
Manual torque boost
frequency adjustment
A043
R/W 0 to 500
0.1 [%]
123Eh
V/F characteristic curve
selection, 1st motor
A044 R/W
0 (VC), 1 (VP), 2 (free V/f),
3 (sensorless vector control)
-
123Fh
V/f gain setting
A045
R/W 20 to 100
1 [%]
1240h
Voltage compensation gain
setting for automatic torque
boost, 1st motor
A046
R/W 0 to 255
1 [%]
1241h
Slippage compensation gain
setting for automatic torque
boost, 1st motor
A047
R/W 0 to 255
1 [%]
1242h
to1244h
(Reserved) -
-
Inaccessible
-
1245h
DC braking enable
A051
R/W 0 (disabling), 1 (enabling), 2 (set frequency only)
-
1246h
DC braking frequency setting
A052
R/W 0 to 40000
0.01 [Hz]
1247h
DC braking wait time
A053
R/W 0 to 50
0.1 [sec.]
1248h
DC braking force during
deceleration
A054
R/W 0 to 70
1 [%]
1249h
DC braking time for
deceleration
A055
R/W 0 to 600
0.1 [sec.]
124Ah
DC braking/edge or level
detection for [DB] input
A056
R/W 0 (edge operation), 1 (level operation)
-
124Bh DC braking force for starting
A057
R/W 0 to 70
1 [%]
124Ch DC braking time for starting
A058
R/W 0 to 600
0.1 [sec.]
124Dh
DC braking carrier frequency
setting
A059
R/W 5 to 120
0.1 [kHz]
124Eh (Reserved)
-
- Inaccessible
-
124Fh
Frequency upper limit setting A061 (high)
R/W
0 or "maximum frequency limit" to "maximum
frequency"
0.01 [Hz]
1250h
Frequency lower limit setting
A061 (low)
R/W 0 or "maximum frequency limit" to "maximum
frequency"
0.01 [Hz]
1251h A062
(high)
R/W
1252h
Jump (center) frequency
setting 1
A062 (low)
R/W
0 to 40000
0.01 [Hz]
1253h A063
(high)
R/W
1254h
Jump (hysteresis) frequency
width setting 1
A063 (low)
R/W
0 to 1000
0.01 [Hz]
1255h A064
R/W
1256h
Jump (center) frequency
setting 2
A065 (high)
R/W 0 to 40000
0.01 [Hz]
1257h
Jump (hysteresis) frequency
width setting 2
A065 (low)
R/W
0 to 1000
0.01 [Hz]
1258h A066
R/W
1259h
Jump (center) frequency
setting 3
A067 (high)
R/W 0 to 40000
0.01 [Hz]
125Ah Jump (hysteresis) frequency
width setting 3
A067 (low)
R/W
0 to 1000
0.01 [Hz]
125Bh A068
R/W
125Ch
Acceleration stop frequency
setting
A069 (high)
R/W 0 to 40000
0.01 [Hz]
125Dh Acceleration stop time
frequency setting
A069 (low)
R/W
0 to 600
0.1 [sec.]
125Eh A070
R/W
Содержание L700 Series
Страница 16: ... Memo ...
Страница 20: ... Memo ...
Страница 22: ... Memo ...
Страница 46: ... Memo ...
Страница 60: ... Memo ...
Страница 62: ... Memo ...
Страница 212: ... Memo ...
Страница 222: ... Memo ...
Страница 224: ... Memo ...
Страница 232: ... Memo ...
Страница 237: ...Chapter 7 Specifications 7 5 L700 300 LFF HFF L700 450 550 LFF HFF 750 HFF 5 Cable hole φ25 5 Cable hole φ41 ...
Страница 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Страница 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Страница 240: ... Memo ...
Страница 242: ... Memo ...
Страница 258: ... Memo ...