Chapter 4 Explanation of Functions
4 - 120
(iii) Writing data to a specified coil [05h]
This function writes data to a specified coil
The following table shows the updating of the coil status.
Coil status
OFF
→
ON
ON
→
OFF
Updating data (upper digit)
FFh
00h
Updating data (lower digit)
00h
00h
(Example)
When sending an operation command to the inverter at slave address "10":
To start the inverter operation, "03" must be set in parameter "A002". Coil 1 is used to turn on an operation
command.
If the function to write data to a coil cannot be executed normally, the inverter will return an exception
response. For details, see Item (viii), "Exception response."
(iv) Writing data to a specified register [06h]
This function writes data to a specified register.
(Example)
When setting "50 Hz" as the base frequency setting (A003) in the inverter at slave address "5":
Since register "1203h" to store the base frequency setting (A003) has a data resolution of 1 Hz, specify
"50" (0032h) as the updating data to set "50 Hz".
If the function to write data to a specified register cannot be executed normally, the inverter will return an
exception response. For details, see Item (viii), "Exception response."
Query
Field name
Sample setting
(hexadecimal)
1
Slave address (*1)
0A
2 Function
code
05
3
Starting coil number
(upper digit) (*2)
00
4
Starting coil number
(lower digit) (*2)
00
5
Updating data (upper digit)
FF
6
Updating data (lower digit)
00
7
CRC-16 code (upper digit)
8D
8
CRC-16 code (lower digit)
41
*1 If this query is broadcasted, no inverter will return any
response.
*2 Note that the starting coil number is 1 less than the
actual coil number of the coil to be read first.
Response
Field name
Sample setting
(hexadecimal)
1
Slave address
0A
2
Function code
05
3
Starting coil number (upper
digit)
00
4
Starting coil number (lower
digit)
00
5
Updating data (upper digit)
FF
6
Updating data (lower digit)
00
7
CRC-16 code (upper digit)
8D
8
CRC-16 code (lower digit)
41
Query
Field name
Sample setting
(hexadecimal)
1
Slave address (*1)
05
2 Function
code
06
3 Starting
register number
(upper digit) (*2)
12
4 Starting
register number
(lower digit) (*2)
02
5
Updating data (upper digit)
00
6
Updating data (lower digit)
32
7
CRC-16 code (upper digit)
AD
8
CRC-16 code (lower digit)
23
*1 If this query is broadcasted, no inverter will return any
response.
*2 Note that the starting coil number is 1 less than the
actual coil number of the coil to be read first.
Response
Field name
Sample setting
(hexadecimal)
1
Slave address
05
2
Function code
06
3
Starting register number
(upper digit)
12
4
Starting register number
(lower digit)
02
5
Updating data (upper digit)
00
6
Updating data (lower digit)
32
7
CRC-16 code (upper digit)
AD
8
CRC-16 code (lower digit)
23
Содержание L700 Series
Страница 16: ... Memo ...
Страница 20: ... Memo ...
Страница 22: ... Memo ...
Страница 46: ... Memo ...
Страница 60: ... Memo ...
Страница 62: ... Memo ...
Страница 212: ... Memo ...
Страница 222: ... Memo ...
Страница 224: ... Memo ...
Страница 232: ... Memo ...
Страница 237: ...Chapter 7 Specifications 7 5 L700 300 LFF HFF L700 450 550 LFF HFF 750 HFF 5 Cable hole φ25 5 Cable hole φ41 ...
Страница 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Страница 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Страница 240: ... Memo ...
Страница 242: ... Memo ...
Страница 258: ... Memo ...