Chapter 4 Explanation of Functions
4 - 141
Register
No.
Function name
Function code R/W
Monitoring and setting items Data resolution
Register
No.
1501h Auto-tuning
Setting
H001
R/W
0 (disabling auto-tuning), 1 (auto-tuning without
rotation), 2 (auto-tuning with rotation)
-
1502h
Motor data selection, 1st motor
H002
R/W
0 (Hitachi standard data), 1 (auto-tuned data), 2
(auto-tuned data [with online auto-tuning
function])
-
1503h
Motor capacity, 1st motor
H003
R/W (*1)
-
1504h
Motor poles setting, 1st motor
H004
R/W
0 (2 poles), 1 (4 poles), 2 (6 poles), 3 (8 poles),
4 (10 poles)
-
1505h
Motor speed constant, 1st motor
H005 (high)
R/W
0 to 80000
0.001
1506h H005
(low)
R/W
1507h
Motor stabilization constant, 1st
motor
H006
R/W 0 to 255
1
1508h to
1514h
(Reserved) -
-
Inaccessible
-
1515h
Motor constant R1, 1st motor
H020 (high)
R/W
1 to 65530
0.001 [
Ω
]
1516h H020
(low)
R/W
1517h
Motor constant R2, 1st motor
H021 (high)
R/W
1 to 65530
0.001 [
Ω
]
1518h H021
(low)
R/W
1519h
Motor constant L, 1st motor
H022 (high)
R/W
1 to 65530
0.01 [mH]
151Ah H022
(low)
R/W
151Bh
Motor constant Io
H023 (high)
R/W
1 to 65530
0.01 [A]
151Ch H023
(low)
R/W
151Dh
Motor constant J
H024 (high)
R/W
1 to 9999000
0.001
151Eh H024
(low)
R/W
151Fh to
1523h
(Reserved) -
-
Inaccessible
-
1524h
Auto constant R1, 1st motor
H030 (high)
R/W
1 to 65530
0.001 [
Ω
]
1525h H030
(low)
R/W
1526h
Auto constant R2, 1st motor
H031 (high)
R/W
1 to 65530
0.001 [
Ω
]
1527h H031
(low)
R/W
1528h
Auto constant L, 1st motor
H032 (high)
R/W
1 to 65530
0.01 [mH]
1529h H032
(low)
R/W
152Ah
Auto constant Io, 1st motor
H033 (high)
R/W
1 to 65530
0.01 [A]
152Bh H033
(low)
R/W
152Ch
Auto constant J, 1st motor
H034 (high)
R/W
1 to 9999000
0.001
152Dh H034
(low)
R/W
152Eh to
153Ch
(Reserved) -
-
Inaccessible
-
153Dh PI proportional gain for 1st motor
H050
R/W 0 to 10000
0.1 [%]
153Eh PI integral gain for 1st motor
H051
R/W 0 to 10000
0.1 [%]
153Fh
P proportional gain setting for 1st
motor
H052
R/W 0 to 1000
0.01
1540h to
1546h
(Reserved) -
-
Inaccessible
-
1549h to
1550h
(Reserved) -
-
Inaccessible
-
1551h
Terminal selection PI proportional
gain setting
H070
R/W 0 to 10000
0.1 [%]
1552h
Terminal selection PI integral gain
setting
H071
R/W 0 to 10000
0.1 [%]
1553h
Terminal selection P proportional
gain setting
H072
R/W 0 to 1000
0.01
1554h
Gain switching time
H073
R/W 0 to 9999
1 [msec.]
1555h to
1600h
(Reserved) -
-
Inaccessible
-
Содержание L700 Series
Страница 16: ... Memo ...
Страница 20: ... Memo ...
Страница 22: ... Memo ...
Страница 46: ... Memo ...
Страница 60: ... Memo ...
Страница 62: ... Memo ...
Страница 212: ... Memo ...
Страница 222: ... Memo ...
Страница 224: ... Memo ...
Страница 232: ... Memo ...
Страница 237: ...Chapter 7 Specifications 7 5 L700 300 LFF HFF L700 450 550 LFF HFF 750 HFF 5 Cable hole φ25 5 Cable hole φ41 ...
Страница 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Страница 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Страница 240: ... Memo ...
Страница 242: ... Memo ...
Страница 258: ... Memo ...