8. Troubleshooting
196
SMGB0079 rev.0 - 01/2013
Phenomenon
Cause
Check item
Action
(Turn OFF the main
switch)
Activation of the high-pres-
sure switch due to the
excessively high discharge
pressure
Insufficient Air Flow to the Heat Exchanger (Outdoor Heat
Exchanger during the Cooling Process or Indoor Heat
Exchanger during the Heating Process)
Check the heat exchanger
for dust or for clogging
Remove the dust or the
clogging
Check the air filter for dust
Remove the dust
Check for any obstacles at
the inlet or the outlet of the
heat exchanger
Remove the obstacles
Check the service area
Secure service area
Check the speed (Outdoor
Fan: Cooling / Indoor Fan:
Heating)
Replace the fan motor if
faulty
Excessively High Temp. Air to the Indoor Unit
Calculate the heat load
Reduce the heat load or
use a bigger unit
Check for hot air near the
ceiling (Heating)
Provide good circulation
Check for short-circuited air
(Heating)
Remove the short-circuited
air
Check for other heat source
Remove the heat source
Faulty High-Pressure
Switch
Faulty Pressure Switch
Measure the discharge
pressure. Check the conti-
nuity after the decrease of
the pressure
Replace the pressure
switch if faulty
Insufficient Contacting
Measure the resistance by
means of the tester
Fix the looseness. Replace
the connector
Incorrect Connection
Check the connections
Repair the connections
Overcharged refrigerant
Check the cycle operation
temp.
Charge the refrigerant
correctly
Mixture of the non-condensate gas in the refrigerant cycle
Check the air temp. and
the pressure
Recharge the refrigerant
after the vacuum pumping
Clogging of the discharge piping
Check for clogging
Remove the clogging
Liquid line stop valve or gas line stop valve is not in
operation
Check the stop valves
Fully Open the stop valves
Faulty Magnet Switch
Incorrect Connection
Check wiring
Repair connections. Re-
place Magnet Switch
Malfunction A Contact
Check connections
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......