8. Troubleshooting
225
SMGB0079 rev.0 - 01/2013
8
Alarm code
35
Incorrect Indoor number setting
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, alarm code and unit model code appear alternately on the Set Temperature display of the remote
control switch. The alarm code also appears on the outdoor unit PCB display.
-
The alarm code appears three minutes after the outdoor unit power activation if duplication is detected in indoor
unit numbers connected to an outdoor unit (one refrigerant system). This applies when indoor unit numbers are
configured using the rotary switch (RSW1).
-
The alarm code appears when the more than next indoor units are connected to one outdoor unit.
Model
Number of Indoor Units
RAS-3HVNPE
RAS-(4-12)H(V)N(P/C)(E)
>11
RAS-(2-2.5)HVNP
RAS-3HVNC
>5
-
The alarm code appears when the indoor and outdoor unit refrigerant system and address are set to 64 or above.
(In such a case, the alarm code “b1” appears on the remote control switch.)
N O T E
The alarm code may appear when H-LINK system is employed for indoor–outdoor unit transmission, if there is
any incorrect setting in DSW4/RSW1 on the outdoor unit PCB and DSW5/RSW2 on the indoor unit PCB; which
are dip switches used for refrigerant system setting. In such a case, turn OFF the power and correctly set DSW4/
RSW1 on the outdoor unit PCB and DSW5/RSW2 on the indoor unit PCB before reactivating the power.
(Some indoor unit models do not have RSW2.)
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......