7. Test run
171
SMGB0079 rev.0 - 01/2013
7
Remote control switch
indication
Unit condition
Wrong portions
Inspection points after power
source OFF
The operation lamp
flickers. (1 time/1 sec.)
and the unit number and
alarm code 03 flicker.
The unit does not start.
The power source of
outdoor unit in not turned
ON.
The connecting wires of
operating line are inco-
rrect or loosened.
1
Connecting order of each ter-
minal boards.
2
Screw fastening of each termi-
nal boards.
N O T E
Recovering method of FUSE for
operating circuit. There is a fuse
(FUSE4 on indoor unit PCB1,
EF1 on outdoor unit PCB1) to
protect operating circuit on the
PCB, when the power lines are
connected to operating lines. If
fuse is melted, operating circuit
can be recovered once by set-
ting the dip switch on the PCB
as shown in
The operation lamp flic-
kers. (1 time/2 sec.)
The unit does not start.
Remote control cable is
broken.
Contact of connectors is
not good.
The connection of remote
control cable is incorrect
This is the same as item
1
and 2
Indication of flicker ex-
cept above
The unit does not start, or start once
and then stops
The connection of ther-
mistor or other connec-
tors are incorrect. Trip-
ping of protector exists,
or else.
Check by the abnormality mode
table in the Technical Catalogue
(Do it by service people).
The operation lamp
flickers. (1 Time/1s)
Unit number
00
, alarm
code
dd
and unit code
E00
flicker
The unit does not start.
The connection of the
remote control cable
between indoor units is
incorrect.
Check by the abnormality mode
table in the Technical Catalog (Do
it by service people).
Back to
after checking
Instructions for the recovery when the fuse of the transmission
circuit is blown out:
1
Correct the wiring to the terminal board.
2
Set pin 2 of DSW7 on the indoor units PCB to ON
Only for RPK-(0.8-1.5): set DSW7 on the indoor unit PCB
ON
Except RPK(0.8/1.5)
Only RPK-(0.8/1.5)
ON OFF
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......