8. Troubleshooting
269
SMGB0079 rev.0 - 01/2013
8
Check mode items
RAS-(2-2.5)HVNP / RAS-3HVNP
Item
Item
Indication data
Check
No.
In-
dic.
In-
dic.
Contents
Input/output state of outdoor micro-
computer
01
SC
Indicates only for the segments corresponding to the equipment in
the figure. (See figure above)
Capacity of operating indoor unit
02
oP 11
00~199
In case that capacity is higher than 100, the last two digits flash
Inverter order frequency to compressor
03
HI 74
0~115 ( Hz)
In case that frequency is higher than 100Hz, the last two digits flicker
Indoor order frequency to compressor
04
H2 74
0~115 ( Hz)
In case that frequency is higher than 100Hz, last two digits flicker
Air flow ratio
05
Fo 80
00~100 (%)
In case that air flow ratio is 100%, “
00
” flashes
Outdoor unit expansion valve opening
06
Eo 30
00~100 (%)
In case that expansion valve opening is 100%, “
00
” flashes
Temperature at the top of compressor
07
d 02
00~142 (ºC)
In case that temperature is higher than 100ºC, the last two digits flash
Evaporating temperature at heating
08
E 2
-19~80ºC
Ambient air temperature
09
o -3
-19~80ºC
Control PCB information
10
F 20
Internal information of the PCB
Control PCB information
11
A1 12
Internal information of the PCB
Inverter secondary current
12
A2 20
00~199 (A)
In case that current is higher than 100ºC, the last two digits flash
Outdoor unit address
13
nA 00
00~63
In case of twin/triple/quad-type unit,
the information of 2nd to the 4th indo-
or units is indicated repeatedly.
The right character of the indication
represents the indoor unit setting No.
Single: A
Twin: A, b
Triple: A, b, c
Quad: A, b, c, d
Indoor unit expansion valve opening
14
EA 20
00~100 (%)
In case that opening is
100%. “
00
” flashes
Liquid pipe temperature of indoor unit
(freeze protection)
15
LA 05
-19~127 (ºC)
Indoor unit intake air temperature
16
iA 28
-19~127 (ºC)
Indoor unit discharge air temperature
17
oA 20
-19~127 (ºC)
Cause of indoor unit stoppage
18
dA 05
(See table at the next page)
Accumulated Operating Time of Com-
pressor
19
UJ 00
0 to 9,999 (x 10 hours)
Alternately upper 2 digits and lower 2 digits are indicated every
0.5 sec.
Accumulated Operating Time of Com-
pressor
20
cU 00
0 to 9,999 (x 10 hours)
Alternately upper 2 digits and lower 2 digits are indicated every
0.5 sec.
Alarm code for abnormal stoppage of
compressor
21
AC 08
Alarm code on compressor
Cause of stoppage at inverter
22
i
1
(See table at the next page)
Abnormal data record
23
n1 00
One of the abnormal data record from latest (n1) to oldest (n9) is
indicated. Alarm code or cause code is indicated.
Total capacity of indoor unit connected
24
CP 22
00~96
In case that capacity is higher than 100, the last two digits flash
Connected indoor unit number
25
AA
2
00~64
Refrigerant adress
26
GA
0
00~63
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...