6. Optional functions
159
SMGB0079 rev.0 - 01/2013
6
Slo defrost setting (
bJ
)
Press “PSW1” and select the setting condition “1” at the slow defrost setting “
bJ
“.
Indoor fan operation is stopped during the defrost operation.
Setting condition*
Indoor fan operation
0
Indoor fan stop during defrost operation
1
Indoor fan SLo during defrost operation
Cancellation of outdoor hot start limit (
H
)
Press “PSW1” and select the setting condition “1” at the cancellation of hot start setting “
H
”, so the hot start protection
control can be canceled.
Long piping setting (
nU
)
Press “PSW1” and select the setting condition “1” at the long piping setting “
nU
”.
If cooling capacity or heating capacity is not enough under the long-distance piping condition, this function can be set the
target compressor frequency higher than normal target value.
Wave function setting (
UE
)
Press “PSW1” and select the setting condition “1”, so that the wave function setting “
UE
”.
While this function is activated, the maximum limit of running current is changed from 60% to 100% as shown in the figure.
Electricity
consumption
(100%)
Electricity
consumption
(60 to 80%)
N O T E
• Wave function can be activated when demand function is selected at one of the input terminal indications
i1
,
i2
and
i3
.
• The minimum limit of running current control is according to the set value of the demand function.
• If demand function is not set at the input terminal indication, this function can not be activated.
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......