4.3.3 Jumpers
Jumper lead setting (JP1~6)
Setting before shipment:
System
JP1
JP2
JP3
JP4
JP5
JP6
Single phase (1~)
0
1
1
1
0
0
Three-phase (3N~)
1
1
0
1
0
0
N O T E
•
0: Open
•
1: Short circuit
The function selection using the jumper lead setting is shown in the tables below:
RAS-(2-2.5)HVNP / RAS-3HVNC
Setting
Function
Details
JP1
Not used
—
JP2
Not used
—
JP3
Not used
—
JP4
Fixing for Cooling Only
When JP4 is set to “open”, operation mode is fixed for cooling. Thermo-ON is available only by
“COOL” or “DRY” mode at indoor unit.
JP5
Selfdiagnosis
For function test of the outdoor unit control PCB.
JP6
Phase detection release
Phase detection abnormaly not detected.
Release of the Momentary Power Failure between S and T phases
RAS-(3-12)H(V)N(P/C)(E)
Setting
Function
Details
JP1
220V power source voltage
When JP1 is set to “open”, changes value of current protection, etc., to 220V power source
voltage.
JP2
415V power source voltage
When JP2 is set to “open”, changes value of current protection, etc., to 415V power source
voltage.
However, in single phase units it becomes 200V power source voltage.
JP3
380V power source voltage
When JP3 is set to “open”, changes value of current protection, etc., to 380V power source
voltage.
However, in single phase units it becomes 200V power source voltage.
JP4
Fixing for Cooling Only
When JP4 is set to “open”, operation mode is fixed for cooling. Thermo-ON is available only by
“COOL” or “DRY” mode at indoor unit.
JP5
Selfdiagnosis
For function test of the outdoor unit control PCB.
Factory default setting is open. When power ON in short condition it enters selfdiagnosis.
JP6
Phase detection release
Phase detection abnormaly not detected. When short, doesn’t affect phase detection.
4.3.4 LED’s indication
LED Indication
LED1
Red
This LED indicates the transmission status between the
indoor unit and the RCS
LED2
Yellow
This LED indicates the transmission status between the
indoor unit and the outdoor unit
LED3
Green
Power source for the PCB
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......