6. Optional functions
158
SMGB0079 rev.0 - 01/2013
Cancellation of Outdoor Ambient Temperature Limit (
GS
)
Press “PSW1” and select the setting condition “0” to “3” at the cancellation of outdoor ambient temperature limit of “
GS
”.
Then, this function can be set.
The heating operation is continued under a high outdoor temperature or the cooling operation is continued under a low
temperature.
Setting condition*
Operation mode for cancellation
0
Not available (default setting)
1
Heating
2
Cooling
3
Heating / Cooling
Cancelled Conditions for Outdoor Unit Ambient Temperature Limit
• Heating Operation
If one of following conditions is continued for 1 second, the unit will be under Termo-OFF.
-
Ta > 23
o
C and Pd > 3.7 MPa
-
Ta > 21
o
C, Ti > 26
o
C and Pd > 3.7 MPa
-
Ta > 15
o
C, Ti > 29
o
C and Pa > 3.7 MPa
• Cooling Operation
If the following condition is continued for 1 second, the unit will be under Termo-OFF.
-
Ta < -7
o
C
Ta: Outdoor Ambient Temperature
Ti: Indoor Air Inlet Temperature
Pd: Discharge Pressure
N O T E
If this function is set and the outdoor unit operates in the stoppage area for a long time, the outdoor unit may be
damaged since protection control is cancelled.
Change of defrost condition (
Jo
)
Press “PSW1” and select the setting condition “1” at the change of defrost condition “
Jo
”.
Example for RAS-(3-12)H(V)N(P/C)(E):
Setting condition
Standard Specifications (factory default state)
Heating specification
Function selection setting
Jo:0
Function selection setting
Jo:1
Temperature
conditions under
defrosting
operation
Содержание EV-1.5N1
Страница 2: ......
Страница 4: ... II ...
Страница 26: ......
Страница 100: ......
Страница 123: ...4 Electrical wiring 109 SMGB0079 rev 0 01 2013 4 4 7 2 RAS 3HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01261_0 ...
Страница 124: ...4 Electrical wiring 110 SMGB0079 rev 0 01 2013 4 7 3 RAS 4 6 HVNPE 1 230V 50Hz U Surface V Surface W Surface XEK01262_0 ...
Страница 128: ...4 Electrical wiring 114 SMGB0079 rev 0 01 2013 4 7 7 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_0 ...
Страница 129: ...4 Electrical wiring 115 SMGB0079 rev 0 01 2013 4 4 7 8 RAS 12HNP 3N 400V 50Hz Preliminary data 317S136064 ...
Страница 130: ...4 Electrical wiring 116 SMGB0079 rev 0 01 2013 4 7 9 RAS 12HNC 3N 400V 50Hz Preliminary data 317S136071 ...
Страница 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Страница 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Страница 158: ......
Страница 196: ......
Страница 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Страница 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Страница 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Страница 324: ...9 Spare parts 310 SMGB0079 rev 0 01 2013 9 6 2 Electrical parts Spare Parts Document EPN 201211B ...
Страница 332: ......
Страница 452: ......
Страница 479: ......